Configuration Of Line Topology With R1 Devices - Siemens SIMATIC S7-1500 System Manual

Redundant system
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

6.3.7.5

Configuration of line topology with R1 devices

Introduction
The section below shows you the configuration of the S7-1500H redundant system with R1
devices in a line topology.
Advantages/benefits
• Less wiring effort required for a line topology compared to ring topologies. Only one
PROFINET line is connected to each of the PROFINET interfaces X1 of the H-CPUs.
• A configuration of the MRP rollers is not required.
• The reconfiguration times of the R1 devices are significantly reduced and shorter
monitoring times are therefore possible.
• Connect the R1 devices in opposite directions as shown in the figure below. The opposing
cabling ensures that in the event of failure or replacement of an R1 device, all other
devices remain available. This increases the availability of the redundant system:
– In the RUN-Redundant system state, replacement of a particular R1 device is possible
– In case of a line interruption of the two PROFINET lines between two neighboring R1
S7-1500R/H redundant system
System Manual, 01/2024, A5E41814787-AF
without failure of the other R1 devices. For more information, refer to the section
Replacing components of the S7-1500R/H redundant system (Page 443).
devices, the redundant system continues to exchange process data with all R1 devices.
For more information, refer to the section Failure of both PROFINET lines between two
R1 devices in a line topology (Page 194).
Application planning
6.3 Configuration versions
161

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-1500r/h

Table of Contents