Application Planning; Requirements - Siemens SIMATIC S7-1500 System Manual

Redundant system
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Application planning

6.1

Requirements

Introduction
Please note the following requirements for use of the S7-1500R/H redundant system.
Hardware requirements
Table 6- 1
Hardware requirements
Property
S7-1500R/H CPUs
Communications processor
CP 1543-1
Active backplane bus
129
Requirement
2 identical R-CPUs or H-CPUs in the redundant system
Identical article numbers and firmware versions for the two CPUs
Firmware version display of the R/H-CPUs: FW version V2.6 or higher
Article number and firmware version of the CP 1543-1 identical (6GK7543-1AX00-0XE0),
FW version V3.0 or higher
Active backplane bus for H system
Active backplane bus ST 1+8 (6ES7590-0BH00-0AA0): FW version V1.1.0 or higher
Active backplane bus ST 1+4 (6ES7590-0BD00-0AA0): FW version V1.1.0 or higher
1)
S7-1500R/H redundant system
System Manual, 01/2024, A5E41814787-AF