Loadctrlsuspend - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series
LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
Menu Path
Parameter
LowfireAdaptPtNo (S)**
O2 CtrlThreshold (S)
LoadCtrlSuspend (S)
Params & Display>
O2Contr/Alarm>
Gas/Oil Settings>
Control Param
O2ModOffset (S)
O2TrimBehavior (O)
SCC Inc.
Default
Range
Sets the point that Tau Low-Fire is automatically measured. Tau and PI for low fire will be
based on this point. A low fire adapt point must be defined before setting up the O2 trim
Not Set
2-15
curves. Typically the low fire adapt point is chosen at point 2, but a higher point may be
necessary on high-turndown burners and / or oversized stacks.
This is the minimum load for the O2 trim. If the load drops below this value, the O2 trim
0%
0-100%
automatically de-activates. 5% above this load setting the O2 trim control will automatically
reactivate. Typically set to the same load value as the load at LowfireAdaptPtNo.
During a load change, the O2 trim will lock and will not actively trim. This is necessary due to
delay time thru the boiler and also different O2 trim setpoints from low fire to high fire.
When locked and not actively trimming, the O2 trim runs on precontrol, meaning that it
5%
0-25%
calculates where to position the air influenced actuators based on burner characteristics
learned by the LMV5 during O2 commissioning. This parameter determines how much of a
load change will lock the O2 trim and cause it to run on precontrol.
During a load change, this offset temporarily increases the air related load (opens the air
influenced actuators). The amount of load change that will trigger O2ModOffset is
determined by the setting of LoadCtrlSuspend . How much the air related load is increased is
0%
0-5%
determined by the setting of this parameter. A setting of 1% should translate into a 1%
increase in measured %O2 during a load change. After active trim is resumed, the offset will
be dissolved.
Sets the behavior of the O2 trim when active (not locked). This setting only applies if
StartMode is set to standard. Three possibilities exist:
1) ForcedAirAdd - O2 trim will add air faster than it will subtract air. Used when the O2
ForcdAirAdd
setpoint is close to the O2 Alarm .
ForcdAir-
ForcdAirRed
Add
2) ForcedAirRed - O2 trim will subtract air faster than it will add air. Used when the O2
symmetric
setpoint is close to O2 MaxValue .
3) Symmetric - O2 trim will add and subtract air at the same rate. Used when the O2
setpoint is approximately midway between the O2 Alarm and O2 MaxValue .
Page 24
HOME
Description
P - LIST
Technical Instructions
LV5-1000
LMV
x x
x x
x x
x x
x x
Section 3