Siemens LMV5 Series Technical Instructions page 348

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Technical Instructions
Document No. LV5-8000
Low Fire Hold with an RWF55 (continued)
Hot Water Boiler with an RWF55 with 3-position Output
1. Set the following parameters in the LMV5:
Params & Display > LoadController > Configuration > LC_OptgMode =
ExtLC X5-03
2. Set the following parameters in the RWF55:
ConF > Inp > Inp1 > SEn1 = type of RTD being used for temperature sensor
ConF > Cntr > CtYP = 1
ConF > AF > FnCt = 7
ConF > AF > AL = temperature to enable low fire hold
ConF > AF > HYSt = deadband around low fire hold temperature
3. Wire the LMV5 and RWF55 as shown in Figure 7:
Figure 7: Low Fire Hold via 3-position Output on a Hot Water Boiler
See page 19 for an example of the low fire hold operation.
Appendix A
Page 18