Siemens LMV5 Series Technical Instructions page 256

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Error
Diag.
Device
Display
Code
Code
B6
B7
B8
B9
BA
BB
BC
BD
C0
E0
E1
E2
LMV5
EA
Load
Internal Fault
A6
EB
Controller
Load Controller
EC
Module
ED
EE
EF
F0
F1
F2
F3
F4
F5
F6
FE
FF
Section 7
Meaning for the LMV5x System
Fault with Base Unit (LMV5) Internal Load Controller
Time block too long: Time block 0
Time block too long: Time block 1
Time block too long: Time block 2
Time block too long: Time block 3
Time block too long: Time block 4
Time block too long: Time block 5
Time block too long: Time block 6
Time block too long: Time block 7
CRC fault in page
Identpower
Controller parameter KP
Scanning time
Invalid branch in EEPROM module()
Invalid branch in EEPROM module()
Invalid branch in EEPROM module()
Invalid branch in EEPROM module()
Invalid branch in EEPROM module()
Invalid branch in EEPROM module()
Fault during ROM test
Fault during RAM test
Fault during RAM test, register bank 0
Fault during RAM test, IDATA range
Fault during RAM test, XDATA range
Stack pointer does not point at stack
Stack overflow
Fault messages in fault management
Fault messages in fault management
If fault occurs sporadically, reduce electrical noise.
If fault occurs continuously, replace LMV5.
Page 48
HOME
Corrective Action