LMV Series
LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
Menu Path
Parameter
Params & Display>
Display Contrast (U)
AZL
ProductionDate (U)
Params & Display>
AZL>
SerialNumber (U)
ProductID
ParamSet Code (U)
ParamSet Vers (U)
Params & Display>
SW Version (U)
AZL
1 AirActuator (S)
2 GasActuat(Oil) (S)
Params & Display>
3 OilActuator (S)
Actuators>
4 AuxActuator (S)

Addressing

5 AuxActuator2 (S)
6 AuxActuator3 (S)
DeleteCurves (S)
1 AirActuator (O)
Params & Display>
2 GasActuat(Oil) (O)
Actuators>
3 OilActuator (O)
DirectionRot
4 AuxActuator (O)
5 AuxActuator2 (O)
6 AuxActuator3 (O)
Params & Display>
ProductionDate (U)
Actuators>
SerialNumber (U)
ProductID>
ParamSet Code (U)
1 AirActuator
ParamSet Vers (U)
SCC Inc.
Default
Range
Adjust as needed
ASN (U)
Read Only
Read Only
1 blink = Air
2 blink = Gas(Oil)
3 blink = Oil
4 blink = Aux 1
5 blink = Aux 2
6 blink = Aux 3
Go into parameter then
press Enter to delete
standard
standard
reversed
ASN (U)
Read Only
Change with < > keys, store with the Enter key, or cancel with the Esc key.
Information concerning the AZL.
Software version on the AZL.
Enables addressing of the actuators. Select one of the actuators and press Enter.
The AZL will then serve as a guide through the rest of the procedure.
This procedure involves pressing a red button (hold about 1s) on the selected actuator. The
actuators can be wired and addressed in any order. The green LED will be on when the
actuator is powered and not addressed, and it will blink after it has been addressed.
NOTE: Holding the red button on the actuator down for approx. 10 sec will clear the
addressing on that actuator.
This deletes the ratio control (fuel / air) curves and the ignition positions. Curves must be
deleted if the direction of rotation on any actuator is to be changed.
Sets the direction of rotation for each actuator, regardless of which fuel is selected.
Looking at the actuator with the shaft pointed at eye:
standard - shaft rotates counterclockwise to open.
reversed - shaft rotates clockwise to open.
These descriptions are opposite if viewed from the cover end of the actuator (shaft pointing
away from eye).
Information concerning the currently addressed air actuator.
Page 37
HOME
P - LIST
Description
Technical Instructions
LV5-1000
LMV
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x
x x
x x x
x x x
x x x
x x x
x x x
x x
x x
x x x
x x x
x x x
x x x
x x x