Most boilers use load controller mode "IntLC" which utilizes the local temperature / pressure sensor and 
a local setpoint entered through the AZL display.  The following procedure outlines how to set up this 
mode: 
 
If possible, shut off the burner switch.  Let the burner get back to Phase 12 (standby). 
1.
 
Verify that the load controller is in the correct mode through the following menu path:  
2.
 
Params & Display > LoadController > Configuration 
 
Set  parameter  LC_OptgMode  to  "IntLC".    Next,  verify  that  the  connected  pressure  or 
temperature  sensor  is  configured  correctly.    In  the  same  menu,  set  Sensor  Select  to 
"PressSensor"  for  a  steam  boiler  or  to  the  appropriate  temperature  sensor  for  a  hot  water 
boiler. 
 
If a pressure sensor was selected, two additional parameters must be set in the same menu.  Set 
3.
parameter Ext Inp X61 U/I to match the pressure sensor wired into the X61 terminal.  Typically 
this  will  be  0‐10VDC  or  4‐20mA  and  will  be  printed  on  the  side  of  the  sensor.    Next,  set 
parameter MRange PressSens to the high range of the pressure sensor.  This is typically printed 
on the side of the pressure sensor. 
 
Configure setpoint W1 (the local setpoint) through the following menu path: 
4.
 
Operation > BoilerSetpoint 
 
Set the turn‐on point (SD_ModOn) and the turn‐off point (SD_ModOff) for the boiler.  These are 
5.
percentages based on the current setpoint (W1).  The menu path for these parameters is: 
 
 
Params & Display > LoadController > ControllerParam 
 
Typically, the burner is shut off 10% over setpoint and turned back on 1% above setpoint. 
 
NOTE:  Other pressure /  temperature controls or limits  on the  boiler must  be set  above the 
SD_ModOff pressure / temperature. 
 
NOTE:    SD_ModOff  and  SD_ModOn  are  only  valid  for  internal  load  controller  modes.  If  the 
LMV5 is in an external load controller mode, SD_ModOff and SD_ModOn are ignored. 
 
If it is safe to do so, turn on the burner switch.  If thermal shock is a concern, allow the boiler to 
6.
warm.  The burner can be put in manual and held at low fire if necessary through the Manual 
Operation menu. 
 
Once  the  boiler  is  up  to  pressure  /  temperature,  is  modulating,  and  is  carrying  normal  load, 
7.
adjust the PID values through the following menu path: 
 
Params & Display > LoadController > ControllerParam > ContrlParamList 
 