10-4: AZL5 Software Version Updates
This section covers all of the revisions that were made to the AZL5 with each new software
release. The software version of any AZL5 module can be found using the following menu path:
Params & Display > AZL > SW Version
The following updates were made with AZL5 software version 0250:
1. The software version of the flash memory has been changed from V02.20 to V02.50.
2. For the load controller inputs 1 / 2 / 4, the following new parameter names have been
assigned:
• Inp1/2/4Selection → Sensor Select
• Inp1/4BerEnd → MeasureRangePtNi
• Inp2TempBerEnd → MRange TempSens
• Inp2PressBerEnd → MRange PressSens
• Inp3Config_I/U → Ext Inp X62 U/I
• Inp3MinSetpoint → Ext MinSetpoint
• Inp3MaxSetpoint → Ext MaxSetpoint
3. When reading fuel usage in liters, a blank has been introduced between the value and the
unit.
4. The transfer of parameter copies from new LMV5 controllers to the backup memory of the
AZL5 is prevented. Copying is not possible and a message is delivered.
5. The default settings of the following parameters have been changed:
• PrepurgeTmeGas: 15 seconds
• MaxTmeLowFire: 45 seconds
• PostpurgePosAir: 15°
• PostpurgePosAux1: 25°
• PostpurgePosAux3: 25°
• PostpurgePosAux3: 25°
• SD_Stage1On: -2%
SCC Inc.
AZL5 Software Update: Version 0220 to 0250
Page 15