13) Actuator position is checked by using one of three methods.  The method used depends upon the phase of the sequence.  
Position Required to Proceed means that the actuators must achieve and hold a certain position for the sequence to proceed.  
Dynamic Position Checking means that the actuator is evaluated by a "time and distance from target" algorithm.  The further 
the actuator is away from its target position, the less time the actuator is permitted to be in that position.  Run‐Time Position 
Checking means that the actuator is expected to be at a certain point in a certain amount of time (based off of the run‐time 
of the actuator). 
 
14) For  direct  spark  oil  fuel  trains,  spark  (ignition)  will  occur  during  prepurge  if  parameter  OilPumpCoupling  is  set  to 
Magnetcoupl and parameter IgnOilPumpStart is set to on in Ph22. 
 
15) If parameter FGR‐PS/FCC is set for PSdeactStby, the status of the FGR pressure switch is not checked in phase 10 or 12.  The 
rest of the sequence is the same as setting this parameter to FGR‐PS.  If parameter FGR‐PS/FCC is set for PS VSD, input X4‐
01.3 must be energized anytime the VSD speed is higher than RotSpeed PS on and de‐energized anytime the VSD speed is 
lower than RotSpeed PS off. 
 
16) Depending on how parameter HeavyOilDirStart is set, input X6‐01.3 has varying sequences.  If this parameter is set for activ 
38/44, input X6‐01.3 must be energized in phase 44.  If this parameter is set for 38/44..62, input X6‐01.3 must be energized 
in phases 44‐62.  If this parameter is set for act 21..62, input X6‐01.3 must be energized in phases 21‐62.  If this parameter is 
set for deactivated, energizing input X6‐01.3 has no effect. 
 
17) Inputs  X5‐03.2  and  X5‐03.3  have  many  functions  depending  on  how  parameter  Config  X5‐03  is  set.    The  settings  are  as 
follows: 
 
LMV5x  std  –  If  parameter  LC_OptgMode  is  set  to  ExtLC  X5‐03,  energizing  X5‐03.2  will  decrease  the  firing  rate,  while 
energizing X5‐03.3 will increase the firing rate. 
LMV2/3 std – If parameter LC_OptgMode is set to ExtLC X5‐03, energizing X5‐03.3 will achieve stage 2 oil, while energizing 
X5‐03.2 will achieve stage 3 oil. 
LMV2/3 inv – If parameter LC_OptgMode is set to ExtLC X5‐03, energizing X5‐03.2 will achieve stage 2 oil, while energizing 
X5‐03.3 will achieve stage 3 oil. 
 
 
 