Siemens LMV5 Series Technical Instructions page 145

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series 
 
 
 
Parameter
BoilerSetpoint  or  Setp AddSensor
ThresholdOn  (% of current setpoint)
ThresholdOff  (% of current setpoint)
StageSetp_Mod  (% of current setpoint)
 
StageLoad
 
MaxTmeMod
 
 
 
 
 
 
 
SCC Inc. 
 
%
 
 
N/A
 
 
50
 
 
80
 
 
80
 
5
 
N/A
Figure 4‐9:  Example of a Time‐based Stepping Start 
Page 27 
HOME
 
 
Value
o
 
300
F
Current setpoint
Measured temperature must go below 
o
 
150
F
ThresholdOn to engage cold start
Cold start will not disengage until 
o
 
240
F
ThresholdOff is met
Defines the necessary temperature 
o
 
240
F
change required to trigger a load step
 
N/A
Determines the size of the load step
Determines the max. time between load 
 
10 min
steps
Technical Instructions 
Document No. LV5‐1000 
 
Notes
 
 
 
 
 
Section 4 
 