b. Make the burner drive to Point 2 immediately after light off. This can be done by setting
parameter StartPointOp to 2 using the following menu path:
Params & Display > RatioControl > Gas Settings > StartPointOp = 2
18. If the burner needs air temperature compensation after light off (most ultra‐low NOx mesh
burners), activate air temperature compensation. Multiple modes of temperature
compensation are available; the most often used mode is "IgnPtWithTC". This mode will enable
temperature compensation after light off and at Point 2 before the O
Temperature compensated light off can be activated using the following menu path:
Params & Display > O2Contr/Alarm > Gas Settings > Startmode > Startmode
NOTE: Air temperature compensation requires an air temperature sensor wired to the
See "
LMV52.440.
more information.
19. The O
trim can now be activated in one of two modes. Mode "conAutoDeac" allows the O
2
trim to work as long as the measured %O
limit (O
MaxValue). If either of these limits is exceeded, the O
2
burner will run on the normal Ratio Control Curves. Mode "O2 Control" also allows the O
to work, except that if the limits are exceeded a lockout will occur. Mode "conAutoDeac" is
typically used. To set the O
Params & Display > O2Contr/Alarm > Gas Settings > OptgMode
20. The O
trim is now commissioned and activated. Some additional tuning may be required
2
depending on the application. See "Post Commissioning Tuning" later in this section for more
information.
SCC Inc.
O
Trim Configuration (Parameterization) Before Commissioning" above for
2
does not exceed the rich limit (O
2
control operating mode, use the following menu path:
2
Page 17
HOME
Technical Instructions
Document No. LV5‐1000
trim engages.
2
Alarm) or the lean
2
trim will deactivate and the
2
Section 6
2
trim
2