Toshiba L5232 Instruction Manual page 105

Electromagnetic flowmeter converter
Table of Contents

Advertisement

Changing the high/low limit value
The following is an example to change the high limit value from +105% to +103%.
To change other high/low limit value setting, select the following functions.
Low limit value
High-high limit value
Low-low limit value
Switch operation
J2: H ALM VAL
J2: H ALM VAL
J2: H ALM VAL
J2: H ALM VAL
J2: H ALM VAL
Note: If a value of 10% or less, or a value of 110% or more is tried to set, *L. Over SPEC. or *H. OVER SPEC.
appears and the value returns to the previously set value.
Try to set a new value again.
Display example
Select J2: H ALM VAL from the setting item selection menu.
The currently set high limit alarm value appears.
+105.0%
The cursor appears.
Press
+105.0%
Change the number of the digit.
To change other digit, press
+103.0%
the cursor to that digit and change the number there.
The display blinks and the set value is displayed for
conformation
Press
+103.0%
disappears and the display returns to the condition that the
setting value is displayed.
Returns to the menu of setting item selection.
- 104 -
J4: L ALM SET
K2: HH ALM SET
K4: LL ALM SET
Description
further to move the cursor to the digit to change.
again to write the data. Then the cursor
MENU/ENT
6F8A0917
under this condition to move