Mitsubishi Electric MELSEC iQ-F Series User Manual page 119

Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

Error code
Error name
30ADH
Parameter error
30AEH
Parameter error
3103H
Certificate read failure
3104H
Certificate read failure
3106H
Certificate read failure
3107H
Certificate read failure
3108H
Certificate read failure
3109H
Certificate read failure
310BH
Certificate read failure
310DH
Client certificate read
failure
310FH
Client certificate read
failure
3200H
Security function error
(Encryption
communication)
3CF1H
Hardware error
3E30H to
Hardware error
3E42H
3E50H to
Hardware error
3E56H
3E60H to
Hardware error
3E63H
3F92H
Memory error
Error details and causes
MQTT connection setting parameter out of
range
Certificate tool setting parameter out of
range
Flash data read error
Flash data Error
Trusted certificate data error
The trusted certificate data is incorrect.
The validity period of the trusted certificate
has expired.
The trusted certificate data is not supported.
The CRL data is incorrect.
Client certificate data error
Private key data error
The certificate has expired.
An error of hardware was detected.
An error of hardware was detected.
An error of hardware was detected.
An error of hardware was detected.
An error was detected in the memory.
Action
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Write the trusted certificate again using Certificate Configuration
Tool for FX5-ENET.
If retries fail with the same error, a possible cause is a hardware
failure of the target module. Please consult your local Mitsubishi
representative.
Write the trusted certificate again using Certificate Configuration
Tool for FX5-ENET.
If retries fail with the same error, a possible cause is a hardware
failure of the target module. Please consult your local Mitsubishi
representative.
Write the trusted certificate again using Certificate Configuration
Tool for FX5-ENET.
If retries fail with the same error, a possible cause is a hardware
failure of the target module. Please consult your local Mitsubishi
representative.
Recheck the trusted certificate data since it is not appropriate.
Write the trusted certificate again using Certificate Configuration
Tool for FX5-ENET.
If retries fail with the same error, use another certificate since the
certificate used is not available.
Recheck the trusted certificate data since it is not appropriate.
Write the trusted certificate again using Certificate Configuration
Tool for FX5-ENET.
If retries fail with the same error, use another certificate since the
certificate used is not available.
Recheck the trusted certificate data since it is not appropriate.
Write the trusted certificate again using Certificate Configuration
Tool for FX5-ENET.
If retries fail with the same error, use another certificate since the
certificate used is not available.
Recheck the CRL data since it is not appropriate. Write the CRL
again using Certificate Configuration Tool for FX5-ENET.
If retries fail with the same error, a possible cause is a hardware
failure of the target module. Please consult your local Mitsubishi
representative.
Write the client certificate again using Certificate Configuration
Tool for FX5-ENET.
If retries fail with the same error, a possible cause is a hardware
failure of the target module. Please consult your local Mitsubishi
representative.
Write the client certificate again using Certificate Configuration
Tool for FX5-ENET.
If retries fail with the same error, a possible cause is a hardware
failure of the target module. Please consult your local Mitsubishi
representative.
Renew the expired client certificate.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and then switch it to RUN mode. If the
error occurs again even after the above action is taken, the
possible cause is a hardware failure of the CPU module. Please
consult your local Mitsubishi representative.
10 TROUBLESHOOTING
10.6 List of Error Codes
10
117