Own Node Setting

Set the IP address of the FX5-ENET.
Item
IP Address Setting
IP Address
Subnet Mask
Default Gateway
Communication Data Code
Opening Method
*1 When the parameter is written without the IP address setting (blank), the following address is set.
192.168.3.251

Operational Setting

Set the destination alive check conditions for socket communication.
Item
Timer Settings for
Change/Set Timer
Data Communication
Value
Destination Alive
Check Start Interval
Timer
Destination Alive
Check Interval Timer
Destination Alive
Check Resend
Count
7 PARAMETER SETTINGS
70
7.3 Basic Setting
Description
Set the IP address of the FX5-ENET.
Set the class and subnet address of the FX5-ENET to the same settings
as those of the external devices that communicate with the FX5-ENET.
Contact the network administrator before setting the IP address.
Set the subnet mask of the FX5-ENET.
When setting the IP address of the default gateway and performing
communication with an external device in another network through a
router, set the subnet mask pattern of the default gateway. All the
devices in the same subnetwork should have a common subnet mask.
The subnet mask setting is not required for communication in a single
network.
Set the default gateway of the FX5-ENET.
Set the IP address of the relay device (default gateway) to access the
external device in another network.
Set a value that satisfies the following conditions as the IP address of
the default gateway.
• The class of the IP address is A, B, or C.
• The subnet address of the default gateway is the same as that of the
FX5-ENET.
• The host address part is not a sequence of "0" or "1".
Select the format of the data to be used for communication.
• Binary: Communicating data in binary code
• ASCII (X, Y octal): Communicating in ASCII code (X, Y octal)
• ASCII (X, Y hexadecimal): Communicating in ASCII code (X, Y
hexadecimal)
Select how to open a connection.
• Do Not Open by Program: Select this item to perform open
processing and open the connection by the external device. Program
for open/close processing is not required.
• Open by Program: Select this item to perform open/close processing
and open/close the connection by a program.
Description
Select whether to change timer values from the default.
The timer operates with its default value when "No" is selected.
Set the time interval between the reception of the last message from the
external device and the start of alive check.
Set the time interval for performing alive check again when no response
is returned from the external device of alive check target.
Set the number of times to perform alive check when no response is
returned from the external device of alive check target.
*1
Setting range
• Blank
• 0.0.0.1 to 223.255.255.254
(Default: Blank)
• Blank
• 0.0.0.1 to 255.255.255.255
(Default: Blank)
• Blank
• 0.0.0.1 to 223.255.255.254
(Default: Blank)
• Binary
• ASCII (X, Y octal)
• ASCII (X, Y hexadecimal)
(Default: Binary)
• Do Not Open by Program
• Open by Program
(Default: Do Not Open by Program)
Setting range
• No
• Yes
(Default: No)
• Unit [s]: 1 to 16383
• Unit [ms]: 100 to 16383000
(Default: 600s)
• Unit [s]: 1 to 16383
• Unit [ms]: 100 to 16383000
(Default: 10s)
1 to 32767
(Default: 3 times)