LUNA2000-2.0MWH Series Smart String ESS
User Manual
Alarm
Alarm
ID
Name
3030
Battery
Module
Fan Fault
3031
Battery
Pack
Temperatu
re
Imbalance
Issue 08 (2022-11-15)
Severity
Possible Cause
Major
Cause ID = 1
1. The fan is short-
circuited.
2. The power supply is
insufficient.
3. The fan is damaged.
4. The fan is stuck.
Minor
Cause ID = 1
Temperature imbalance
occurs between cells in
the battery pack.
Copyright © Huawei Technologies Co., Ltd.
10 Alarm Reference
Suggestion
1. Determine the positions of the
input and output circuit breakers
of the ESC corresponding to
[ESR-CabinetNo ESM-SlotNo].
2. Issue a shutdown command,
turn off the switch on the
battery side, the switch on the
bus side, and the AC power
supply switch, and wait for 5
minutes.
3. Replace the fan if it is damaged,
clear the foreign matter if there
are any, and rectify power supply
failure if any.
4. Turn on the AC power supply
switch, the switch on the battery
side, and the switch on the bus
side in sequence, and issue a
startup command.
5. If the alarm persists, contact
your dealer or technical support.
1. Determine the positions of the
input and output circuit breakers
of the ESC corresponding to
[ESR-CabinetNo ESM-SlotNo].
2. Issue a shutdown command,
turn off the switch on the
battery side, the switch on the
bus side, and the AC power
supply switch, and wait for 5
minutes.
3. Check whether an air
conditioner or battery pack fan
has generated a fault alarm.
Rectify the fault based on the
alarm handling suggestions.
4. Turn on the AC power supply
switch, the switch on the battery
side, and the switch on the bus
side in sequence, and issue a
startup command.
5. If the alarm persists, contact
your dealer or technical support.