LUNA2000-2.0MWH Series Smart String ESS
User Manual
4.
Issue 08 (2022-11-15)
Figure 8-7 Parameter settings after device search
Parameter
Running under Grid
connection state
Microgrid compatibility
Grid Code
Connect to the power meter.
Copyright © Huawei Technologies Co., Ltd.
8 SmartLogger Web-based Deployment
Description
You need to set this parameter only for the PCS,
but not the SUN2000.
– In the on-grid scenario, set this parameter to
On-grid(PQ).
– In the off-grid scenario, set this parameter to
Off-grid(VSG).
– In the on-grid scenario, set this parameter to
Disable.
– In the off-grid scenario, set this parameter to
Enable.
Set this parameter based on the grid code of the
country or region where the devices are used.
163