Step 1 Remove the fire cylinder.
Step 2 Fill the fire cylinder with extinguishant.
Step 3 Install the fire cylinder.
----End
Issue 02 (2021-11-15)
NO TE
This document does not provide details about how to fill the fire cylinder with
extinguishant. Perform this operation in a dedicated station.
Extinguishant Chemical: HFC-227ea.
Extinguishant weight: 26 kg (maximum: 27 kg).
Purity requirement: not less than 99.9%.
Fire cylinder pressure: 2.5 MPa at 20°C. (verified by filling nitrogen)