Alar
Alarm
m ID
Name
3835
Rectifier
Communi
cation
Failure
3836
Rectifier
Power
Failure
3837
Rectifier
Output
Overvolta
ge
3838
T/H
Sensor
Communi
cation
Failure
3839
Air
Condition
er
Communi
cation
Failure
3840
CO
Sensor
Communi
cation
Failure
3841
H
2
Sensor
Communi
cation
Failure
3842
ESU
Communi
cation
Failure
Issue 02 (2021-11-15)
Severit
Possible Causes
y
Major
Cause ID=1-6
1. The rectifier has been
removed.
2. The rectifier is faulty
and not working.
Major
Cause ID=1-6
The AC loop is
disconnected.
Major
Cause ID=1-6
Lockout has occurred due
to output overvoltage.
Minor
Cause ID=1
T/H sensor
communication failed.
Minor
Cause ID=1-13
Air Conditioner
communication failed.
Minor
Cause ID=1-6
CO Sensor
communication failed.
Minor
Cause ID=1
H
sensor 1
2
communication failed.
Minor
Cause ID=1-6
ESU communication
failed.
Copyright © Huawei Technologies Co., Ltd.
Troubleshooting Suggestions
1. Remove rectifier and then insert it 1
minute later.
2. Replace rectifier or the monitoring
module.
3. If the fault persists, contact your
dealer or Huawei technical support.
1. Check whether the AC input is
normal. If the input is normal,
replace rectifier.
2. If the fault persists, contact your
dealer or Huawei technical support.
1. Remove rectifier and then insert it 1
minute later.
2. If the fault persists, contact your
dealer or Huawei technical support.
1. Check whether the communications
cable of the device is correctly
connected.
2. Check whether the power supply of
the device is normal.
10 Alarm Reference