Table 10-2 Common fault alarms of the intelligent battery cluster controller
Alar
Alarm
m ID
Name
3014
Cluster
controller
exception
3015
Cluster
controller
battery
overvolta
ge
3016
Cluster
controller
battery
undervolt
age
Issue 02 (2021-11-15)
NO TE
● The ESC-No ID is the same as that displayed on the app. The ID is 1 on the left and 2 on
the right. A maximum of two ESC-No IDs are supported.
● The ESR-CabinetNo ID is the same as that displayed on the app. The ID is 1 on the left
and 2 on the right. A maximum of two ESR-CabinetNo IDs are supported.
● ESM-SlotNo indicates the slot number of the battery module.
Severit
Possible Causes
y
Major
Cause ID = 1-34
A serious fault occurs in
the internal circuit of
the cluster controller.
Major
Cause ID = 1-3
Battery cables are
incorrectly connected,
or the battery voltage
exceeds the maximum
operating voltage of the
power module.
Major
Cause ID = 1-3
Batteries are not
securely connected or
are abnormal.
Copyright © Huawei Technologies Co., Ltd.
Troubleshooting Suggestions
1. Determine the position of the input
and output circuit breakers associated
with [ESC-No].
2. Send a shutdown command, turn off
the battery switch and then the bus
switch, and wait for 5 minutes.
3. Turn on the battery switch and then
the bus switch to deliver a startup
command.
4. If the alarm persists, contact your
dealer or technical support.
1. Check whether a battery module
overvoltage alarm is generated in the
cluster. If yes, clear the alarm by
referring to the handling suggestions.
2. Determine the position of the input
and output circuit breakers associated
with [ESC-No].
3. Send a shutdown command, turn off
the battery switch and then the bus
switch, and wait for 5 minutes.
4. Check the cable connection to the
battery side of the power control
module by referring to the
maintenance manual.
5. After verifying that the battery power
cable is correctly connected, turn on
the battery switch and bus switch in
sequence to send a startup
command.
6. If the alarm persists, contact your
dealer or technical support.
10 Alarm Reference