Table 2-35 Technical specifications of the heat detector
Technical Specifications
Model
Dimensions
Operating voltage
Net weight
Alarm category
Enclosure material
Cabling mode
Operating current
Operating temperature
Humidity
Protected area
Applicable base
IP rating
Table 2-36 Indicator description
Item
Indicators

2.8.4.8 Smoke Detector

The smoke detector can detect the smoke concentration in the environment.
Figure 2-44 Appearance of the smoke detector
Issue 02 (2021-11-15)
Heat Detector
55000-121
100 mm diameter x 42 mm height
Supply voltage: 9 V to 33 V
Approx. 80 g
A1R
Polycarbonate, white
Non-polarized two-wire system
Monitoring status < 55 μA @24 V DC; alarm status
< 52 mA
-20°C to +90°C
≤ 95% RH (non-condensing)
About 50 m
GB50116-2013 Code for Design of Automatic Fire
Alarm System
45681-200
IP54
Color
Red
Copyright © Huawei Technologies Co., Ltd.
2
(storey height ≤ 8 m), referring to
Status
Steady on
Blinking
2 Overview
Description
Enters alarm
status
Enters monitoring
status
57