Modbus Exception Responses; Operating Mode; Operating Mode Modbus Coils - ABB SM3000 User Manual

Multipoint videographic recorder
Hide thumbs Also See for SM3000:
Table of Contents

Advertisement

SM3000
Multipoint Videographic Recorder
B.3.2 Modbus Exception Responses
If the instrument detects one of the errors listed in Table B.1
while receiving a message from the host system, it replies with a
response message consisting of the instrument's Modbus
address, the function code, the error code and error check
fields.
Code
Name
01
Illegal Function
02
Illegal Data Address
03
Illegal Data Value
Negative
07
Acknowledgment
08
Memory Parity Error
Table B.1 Modbus Exception Responses
132
Definition
The message function received is
not an allowable action
The address reference in the data
field is not an allowable address
The value referenced in the data
field is not allowable in the
addressed slave
Received message error
Parity check indicates an error in
one or more of the characters
received
B.4 Operating Mode
B.4.1 Operating Mode Modbus Coils
Tables B.2 to B.17 detail the contents of each Modbus coil.
Each coil is assigned a register that can have one of two values:
0000 or 0001.
Modbus Coil
Analog
(Read Only)
Input
0 = Input OK
1 = Input failed
A1
0001
A2
0002
A3
0003
A4
0004
A5
0005
A6
0006
B1
0007
B2
0008
B3
0009
B4
0010
B5
0011
B6
0012
C1
0013
C2
0014
C3
0015
C4
0016
C5
0017
C6
0018
Table B.2 Analog Input Fail States
Appendix B – Modbus Guide
Modbus Coil
Analog
(Read Only)
Input
0 = Input OK
1 = Input failed
D1
0019
D2
0020
D3
0021
D4
0022
D5
0023
D6
0024
E1
0025
E2
0026
E3
0027
E4
0028
E5
0029
E6
0030
F1
0031
F2
0032
F3
0033
F4
0034
F5
0035
F6
0036
IM/SM3000–EN Rev. L

Advertisement

Table of Contents
loading

Table of Contents