ABB SM3000 User Manual page 101

Multipoint videographic recorder
Hide thumbs Also See for SM3000:
Table of Contents

Advertisement

SM3000
Multipoint Videographic Recorder
IM/SM3000–EN Rev. L
Set the value the totalizer counts from and the value applied
when the totalizer is reset.
Set the value at which the totalizer stops or wraps.
Note. A counter configured to count up must have a 'Preset
count' value lower than the 'Predetermined count' value. A
counter configured to count down must have a 'Preset count'
value greater than the 'Predetermined count' value.
Set the required number of decimal places on the higher of the
'Preset count' value or 'Predetermined count' value.
Set the value at which a digital source is activated. This can be
used as an alarm threshold to indicate when the 'Predetermined
count' value is about to be reached.
Select a signal source to reset the totalizer on a rising edge.
Refer to Appendix A on page 129 for a description of the
available sources.
Select the frequency with which totalizer values are added to the
Totalizer log.
Log update time
Log updated every...
5 minutes 0, 5, 10, 15... etc. minutes past the hour
10 minutes 0, 10, 20, 30,...etc. minutes past the hour
15 minutes 0, 15, 30, 45 minutes past the hour
20 minutes 0, 20, 40 minutes past the hour
30 minutes 0, 30 minutes past the hour
60 minutes On the hour
2 hours Midnight, 2am, 4am, etc.
3 hours Midnight, 3am, 6am, etc.
4 hours Midnight, 4am, 8am, etc.
8 hours Midnight, 8am, 4pm, etc.
12 hours Midnight, 12am
24 hours Midnight
Select a signal source to trigger the addition of the current
totalizer values to the Totalizer log on a rising edge. Refer to
Appendix A on page 129 for a description of the available
sources.