M+Camerarecord-E_Axis_Virtualinputcontrol_R; Overview; Labels - Mitsubishi Electric MELSEC iQ-R Series User Manual

Camera recording package
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

9.3

M+CameraRecord-E_AXIS_VirtualInputControl_R

Overview

This FB enables or disables the execution trigger of the recording event set to the network camera manufactured by Axis
Communications that is connected to the MELSEC iQ-R series Ethernet module or RnENCPU network part.
M+CameraRecord-E_AXIS_VirtualInputControl_R
(1)
B:i_bEN
(2)
UW:i_uIO
(3)
UW:i_uConnectionNo
(4)
S:i_sUsername
(5)
S:i_sPassword
(6)
UW:i_uVirtualInputPortNo
(7)
B:i_bVirtualInputPortState

Labels

Input labels
No.
Variable name
Name
(1)
i_bEN
Execution command
(2)
i_uIO
Start I/O number
(3)
i_uConnectionNo
Connection number
(4)
i_sUserName
User name
(5)
i_sPassWord
Password
(6)
i_uVirtualInputPortNo
Virtual input port
number
(7)
i_bVirtualInputPortState
Virtual input port
status
*1 For the RnENCPU (network part), the effective range is 17 to 64 because only the Ethernet port (P1) can be connected.
Output label
No.
Variable name
Name
(8)
o_bENO
Execution status
(9)
o_bOK
When the FB
completed
successfully
(10)
o_bErr
When the FB
completed with an
error
(11)
o_uErrId
Error code
9 FB LIBRARY DETAILS (FOR MELSEC iQ-R SERIES MODULES (RJ71EN71, RnENCPU (NETWORK PART))
(8)
o_bENO:B
o_bOK:B
(9)
o_bErr:B
(10)
o_uErrId:UW
(11)
Data type
Effective
range
Bit
On or off
Word [unsigned]
0H to 0FEH
*1
Word [unsigned]
17 to 128
String (255)
4 to 14
characters
String (255)
4 to 64
characters
Word [unsigned]
1 to 32
Bit
On or off
Data type
Initial value
Bit
Off
Bit
Off
Bit
Off
Word [unsigned]
0
9.3 M+CameraRecord-E_AXIS_VirtualInputControl_R
Description
On: The FB is activated.
Off: The FB is not activated.
Set the start I/O number.
Start I/O number of own station/own node (upper 3 digits of
4 hexadecimal digits)
Specifies the connection number.
17 to 64: Connection numbers 17 to 64 of the Ethernet port
(P1)
65 to 128: Connection numbers 1 to 64 of the Ethernet port
(P2)
Specifies the user name registered in the corresponding
network camera.
(Available strings: a to z, A to Z, 0 to 9)
Specifies the password registered in the corresponding
network camera.
Specifies the port number of the virtual input to be enabled/
disabled.
Page 22 Recording Event Settings
On: The virtual input port status is enabled.
Off: The virtual input port status is disabled.
Description
On: The execution command is on.
Off: The execution command is off.
The on state indicates that sending the command for
switching the virtual input port has been completed.
The on state indicates that an error has occurred in the FB.
The error code of an error occurred in the FB is stored.
9