External device configuration
Set the network camera to be connected.
[Navigation window]  [Parameter]  [Module Information]  Module to be used  [Port (n) Module Parameter] 
[Basic Settings]  [External Device Configuration]
1.
From "Module List", select "Active Connection Module" and drag and drop it to "List of devices" or "Device map area".
2.
For the selected "Active Connection Module", configure the following.
• Communication Method (Socket Communication)
• Port No. of PLC (1 to 4999, 5010 to 65534)
• IP Address of Sensor/Device (IP address of the network camera)
• Port No. of Sensor/Device (80)
• Existence Confirmation (KeepAlive)
• When setting Ethernet port 1, set No.17 to 64 because No.1 to 16 cannot perform socket communications.
• A PLC port number from 1 to 1023 is used as a reserved port number (WELL KNOWN PORT NUMBERS)
generally, and a number from 61440 to 65534 is used in other communication functions. A number from
1024 to 4999 or 5010 to 61439 is recommended.
• Set 80 to the port number of sensor/device.
3.
Click the [Close with Reflecting the Setting] button and click the [Apply] button in the module parameter.
5 PROGRAMMABLE CONTROLLER SETTINGS
5.2 MELSEC iQ-R Series RJ71EN71, RnENCPU (Network Part)
5
39