Rexroth IndraDyn A
Setting of the inlet temperature
DOK-MOTOR*-MAD/MAF****-PR03-EN-P
Observe the temperature range permitted and consider the existing
ambient temperature when setting the coolant inlet temperature.
The lower limit of the recommended coolant inlet temperature can be
limited compared to the existing ambient temperature. To avoid
condensation, a value of max. 5°C below the existing ambient
temperature is permitted as the lowest temperature to be set.
Example 1:
Permitted coolant inlet temperature range +10... +40°C
Ambient temperature: +20°C
Set coolant inlet temperature: +15... +40°C
Example 2:
Permitted coolant inlet temperature range +10... +40°C
Ambient temperature: +30°C
Set coolant inlet temperature: +25... +40°C
Note:
The coolant inlet temperature must be set in a temperature
range of +10°C - +40°C and may be only max. 5°C under the
existing ambient temperature to avoid condensation.
9-13
Application Notes