Activated 2-Zone/Address Dependent Zone/Address (H4/U4) - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512 v2.3.x
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
26.4
Action
"Access"
Scroll to menu H4.
"A"
Scroll to menu U4.
"A"
or
"1"
"Return"
Rev: 1
Activated 2-zone/address dependent
zone/address (H4/U4)
("Two unit dependent" in Win512): When only one zone or one
zone / address (alarm point) is in alarm status
are blinking (0.4 / 0.4 sec.), the buzzer (in the c.i.e.) sounds (0.8 / 5
sec.) and there is a Co-incidence alarm presentation in the c.i.e.
display.
The unit(s) or zone(s) in Co-incidence alarm status is (are) shown in
this menu, from which it is also possible to get a print-out.
Text in display
Co-incidence alarm detector ZZZ/AA
User definable text message (if progr.)
or
Co-incidence alarm zone ZZZ
User definable text message (if progr.)
Present system status on display and
printer
Disablement
Printout: (1=yes)
Activated 2-zone/address dependent
zone/address
Printout: (1=yes)
When "A" is pressed, the active zone & address (or zone)
will be shown in the display, e.g:
Co-incidence alarm detector ZZZ/AA
or
Co-incidence alarm zone ZZZ
Printing started. To stop printing press
C and 0 simultaneously
Activated 2-zone/address dependent
zone/address
Printout: (1=yes)
76
When two or more zones or units (zone / addresses), dependent on each
other, are in alarm status at the same time, normal fire alarm will be activated
in the system.
Operating Instructions Fire alarm system EBL512 V2.3.x
ACCEPT? H4
ACCEPT?
91
76
, the LEDs "Fire" (L1)
Comments
One alarm point or zone
has activated a Co-
incidence alarm.
ZZZ = zone number
AA = address
According to chapter
"Access", see page 72.
U1
Press "1" for an automatic
print-out.
U4
Press "A" for presentation
in the display.
This is a list in which you
can scroll. If there are no
"alarms" and if "Return" is
pressed, menu U4 will be
L
shown again.
L
Press "A" and menu U4
will be shown again.
Scroll or press "Return" to
menu H4. Scroll or press
U4
"Return" to log off.

Advertisement

Table of Contents
loading

Table of Contents