Push button
P1
Alarms queued (black)
P2
Silence buzzer
(yellow)
P3
Silence Alarm devices
(red)
P4
Reset (green)
P5
Evacuate (green)
Operating Instructions Fire alarm system EBL512 V2.3.x
Push buttons on the Fire Brigade Panel (FBP)
Operation/function
Used, when LEDs "Alarms queued" (L2) are lit, to
scroll/browse through the queued alarms (zones). Function,
see chapter "Fire alarm", page 34, under LEDs "Alarms
queued".
Used to silence the buzzer in the c.i.e.
Used to silence the sounders (i.e. to "reset" outputs for alarm
devices).
Used to reset the fire alarm(s).
sec. (In the Belgian, British Standard and British Standard
Marine Application conventions has "P3" to be activated
before "P4" can be used.
10
Used to activate the sounders (i.e. the outputs for alarm
devices).
(CP LED indicators on next page)
9
Multiple reset (Default): All fire alarms in the system will be reset
simultaneously. Single reset: The fire alarm displayed in the LCD (first row
to the left) will be reset. When more than one fire alarm is generated (LEDs
"Alarms queued" are lit) each fire alarm has to be individually reset. Single
encapsulated reset: Fire alarm reset like "Single reset". Encapsulation
function described in EBL512 Planning Instructions, chapter "System
properties (settings).
NOTE (1)! When "Multiple reset" or "Single reset" is used, encapsulated
reset can be done by pressing "Reset" (P4) and 0.1 sec. later also press
"Alarms queued" (P1) and hold them pressed for > 0.5 sec.
By Single reset: The fire alarm displayed in the LCD (first row to the left)
will be encapsulated.
By Multiple reset: The fire alarm displayed in the LCD (first row to the left)
will be encapsulated or the points in alarm status within one zone will be
encapsulated or the whole zone (conventional) will be encapsulated.
NOTE (2)! When "Single reset" or "Single encapsulated reset" is used you
can make a "Multiple reset" by pressing "Reset" (P4) and 0.1 sec. later also
press "A" (in the keypad) and hold them pressed for > 0.5 sec.
10
The "Evacuate" function is valid in the Belgium, British Standard,
Hungarian and Ukrainian conventions. In "Chinese" convention this button
is used for "LED test". In "Polish" (CNBOP) convention this button can be
used for "Alert Annunciation Acknowledge". In "Australian" convention this
button is used to disable all zones "in alarm".