Operating Instructions Fire alarm system EBL512 V2.3.x

Fault messages

Below follows a list of all fault messages, in alphabetical order:
FAULT: 1580 8 zones board x, CU xx
(8 zones expansion board, DET8)
Fault on / no communication to 1580 board No. x in control unit No.
xx. Check address setting and connections on the board.
programming (Win512).
FAULT: 1581 Relay board x, CU xx
(8 relays expansion board)
Fault on / no communication to 1581 board No. x in control unit No.
xx. Check address setting and connections on the board.
programming (Win512).
FAULT: 1582 FBP interface board x, CU xx
(External Fire Brigade Panel interface board)
Fault on / no communication to 1582 board No. x in control unit No.
xx. Check address setting and connections on the board.
programming (Win512).
FAULT: 1583 Extinguishing system, CU xx
Fault in the extinguishing system / equipment connected to the 1583
German Fire Brigade Panel interface board, in control unit No. xx.
FAULT: 1583 GFBP interface board, CU xx
(German Fire Brigade Panel interface board)
• Fault on / no communication to 1583 board in control unit
No. xx. Check address setting and connections on the board.
Check programming (Win512).
• Check the fuses F1 and F2 on the 1583 board.
FAULT: 1584 Autronica board x, CU xx
(Autronica interface board)
Fault on / no communication to 1584 board No. x in control unit No.
xx. Check address setting and connections on the board.
programming (Win512).
45
Check
Check
Check
Check