Activate Alert Annunciation Function (H8/S6) - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512 v2.3.x
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
30.7
Action
"Access"
Scroll to menu S6.
"A"
"A"
Rev: 1
De-activate alert annunciation function
(H8/S6)
Normal function (1):
For alarm points / zones programmed for Alert Annunciation (via
Win512) is normally this function enabled via a time channel, e.g.
enabled daytime (during working hours) and disabled night time.
As an alternative for alarm points / zones programmed for Alert
Annunciation can this function be continuously enabled.
Off (0)
Via this menu (H8/S6) it is possible to de-activate (disable) the AA
function, i.e. the AA function will be disabled for the alarm points /
zones programmed for Alert Annunciation in spite of the time channel
is "on" or if they are programmed to be continuously enabled.
The AA function will stay de-activated (disabled) until re-activated
(re-enabled) again via this menu.
Text in display
De-activate alert annunciation function
Alert annunciation function? 1
(1 = Normal, 0 = Off)
De-activate alert annunciation function
Operating Instructions Fire alarm system EBL512 V2.3.x
ACCEPT?
ACCEPT?
ACCEPT?
125
Comments
According to chapter
"Access code for
maintenance", see page
119.
S6
Write "0" or "1" and press
"A" to accept.
Scroll or press "Return" to
return to menu H8. Scroll
S6
or press "Return" to log
off.