Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
Rev: 1
15.2.5
15.3
15.4
Operating Instructions Fire alarm system EBL512 V2.3.x
Co-incidence alarm
Co-incidence alarm is automatically reset (i.e. when the zone / alarm
point is no longer in alarm status). See also chapter "2-zone / address
dependence (co-incidence alarm)", page 38.
Heavy smoke / heat alarm reset
If a heavy smoke / heat alarm has been activated, it will be reset at the
same time as the corresponding fire alarm is reset. Also the output(s)
will be reset, i.e. de-activated.
Key cabinet alarm reset
Not valid for the DBI (Danish) convention, see chapter "Key cabinet
alarm, DBI convention", page 40.
After reset of the key cabinet alarm ("fire alarm"), a fault message is
shown in the display to inform the user that the key cabinet has been
opened.
FAULT: Key cabinet, control unit: xx
Date: MM-DD
If the key cabinet is closed again, the "status" information
"Serviced" is added.
This key cabinet fault message is to be acknowledged the same way as
a "normal" fault, see chapter "Fault acknowledge", page 60.
When the key cabinet fault is acknowledged, the LED "General fault"
(L7) will be turned OFF (if the key cabinet is closed and if there are
no other faults in the system).
43
Time: HH:MM