Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
Rev: 1
18.3
18.4
Operating Instructions Fire alarm system EBL512 V2.3.x
Now, an automatic reset/restart will take place (see chapter "Restart",
page 69.
If the download was not okey the following text message will be
shown:
Checksum fault in downloaded data.
Control unit will now restart
Now, an automatic reset/restart will take place (see chapter "Restart",
page 69.
After the reset/restart another text message will be shown in the
display:
FAULT: Site specific data (SSD), CU nn
Date: MM-DD
This text message means that the SSD have not been downloaded, i.e.
a new download has to be performed.

Control Units in a TLON network

The SSD for all control units can be downloaded via one control unit.
Start the download from Win512.
performed to the control units, one at a time, according to the chapter
"Single Control Unit" above.
When the download to a control unit is completed, an automatic
reset/restart will take place in that control unit (see chapter "Restart",
page 69.

User definable text messages download

When a fire alarm is activated (e.g. an addressable alarm point), the
presentation number (Zone & Address) will be shown on the first row
in the control units' and the ext. FBP:s' alphanumeric display.
the second row will be shown a user definable text message if
programmed.
Each alarm point can have a unique text message. When several
alarms are activated (in one or more zones) and only the zone numbers
are shown, each zone can have a unique text message.
Each zone line input can have a unique text message.
The user definable text messages will be printed out when a printer is
available.
60
Downloading is performed in a consecutive order, i.e. 0-1-2-3-4-......-29
(amongst the selected control units) but the control unit where the PC is
connected will automatically be the last one to get the SSD downloaded.