Panasonic EBL512 Operating Instructions Manual page 76

Fire alarm system ebl512 v2.3.x
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
The zone(s) will stay in test mode until the test mode is ended but after 60 minutes or if you press
"Return" two times, you will be logged out from menu H1.
Perform the test as quickly as possible, since the output(s) for routing equipment (fire brigade tx) are disabled
(also the parts of the zones in test mode, not visible for the test personnel, are disabled).
In order to shorten the testing time, any time delay for the detectors / zones in test mode will be "disabled",
i.e. fire alarm will be detected faster than normally.
In the tested alarm point, the LED will light up, and the LEDs "Fire" (L1) in the c.i.e. will light up, about ten
seconds, then the alarm point will be automatically reset. The printer, if available, will print out every tested
alarm point (Zone: xxx Address: xx Time: HH.MM).
A sensor in test mode will not be able to activate fault.
After 60 minutes or
"Return"
"Return"
(When required:
"Access", "code")
"A"
"A"
Some national regulations also require a routine test of the routing equipment. Press "A" for no test and press
"1" and "A" to start such a test. The following will happen (in the system):
• The c.i.e. "Fault tx" output will be de-activated
A 60 seconds count-down starts.
• After 30 seconds, also the c.i.e. "Fire brigade tx" output (and corresponding programmable outputs
type 4 = routing equipment) will be activated, indicated by the LED "Fire brigade tx" (L15).
• After another 30 seconds, the test will be ended and the outputs and LEDs will return to "normal".
"1", "A"
"A"
Rev: 1
Zones in test mode: 001, 002, 003, 004
NOTE! See chapter "Alphanumeric display in the
control unit", page 20 regarding priority order.
Zone in TEST MODE:
001 002 003 004
Test of routing equipment? 0
(1 = Yes, 0 = No)
Test of routing equipment in progress.
nn seconds left.
Monthly test is completed!
Perform monthly test
NOTE! During the test, the following information will be shown in
all other c.i.e. displays:
Zones in test mode: 001, 002, 003, 004
(In DBI (Danish) convention, only one zone.)
71
NOTE! This output is activated in normal state.
Operating Instructions Fire alarm system EBL512 V2.3.x
End test:
ACCEPT
ACCEPT
71
, indicated by the LED "Fault tx activated" (L11).
ACCEPT
ACCEPT? H1
74
You are no longer in menu
H1 but still in test mode.
Press "A" to end the test
mode.
The LED "Test mode" is
turned OFF.
"nn" starts at 60 and will
count down to 00.
Scroll or press "Return" to
log off.