Fault - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512 v2.3.x
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
Rev: 1
16
Operating Instructions Fire alarm system EBL512 V2.3.x

Fault

In case of a fault condition, the following has happened / will happen
in the control unit:
• The buzzer in the c.i.e. sounds continuously (steady ON).
• Output for routing equipment (Fault tx) is activated.
• Programmable output(s) for general fault is (are) activated
and output(s) for general charge fault might be activated.
• LED "Fault tx activated" (L11) is turned ON (indicating that
the output for routing equipment (Fault tx) is activated).
• LED "General fault" (L7) is turned ON.
• LEDs "Fault / Disablements Alarm devices" (L13),
"System fault" (L14) and/or "Fault / Disablements Fire
brigade tx" (L15) might be turned ON as well.
• A fault message incl. date and time is shown in the display.
Example; fault message:
FAULT: No reply techn.no. xxxxxx
Date: MM-DD
• If more than one fault is activated, the text:
"More faults"
• If a fault has been corrected before it has been
acknowledged, the "status" text:
after the time.
• Fire alarm presentation has higher priority than the fault
messages. During fire alarm presentation the faults can be
shown via the special fire alarm menu X1, see page 36.
Faults have to be acknowledged, which is done via menu H6 (see page
116). This menu is a list of all not acknowledged and acknowledged
but not corrected faults.
If a fault can not be corrected, it is important to contact service
personnel / engineer immediately.
Note!
As a warning, faults (and disablements) are also indicated by a 2-sec.
beep when an open c.i.e. door is being closed.
52
For faults generated in other control units, the buzzer can be suppressed.
Suppressed / not suppressed is set via Win512 (Control Unit Properties).
53
In Win512, fault latching or not fault latching can be selected.
Fault latching (default) = the faults always have to be acknowledged.
Not fault latching = corrected faults will automatically be removed from the
fault list (menu H6).
44
Time: HH:MM
is added after the time.
"Serviced"
53