Re-Enable Non-Reset Zone / Address (H2/B7) - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512 v2.3.x
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
24.7
Action
"Access"
Scroll to menu H2:
"A"
Scroll to menu B7.
"A"
"A"
Rev: 1

Re-enable non-reset zone / address (H2/B7)

See chapter "Single encapsulated reset (Zone/Detector not reset)",
page 42.
LED "Disablements" (L8) blinking is indicating that one or more
alarm points have been "encapsulated" and have to be re-enabled
before they can generate a fire alarm again.
Text in display
Disable or re-enable
Disable zone
Re-enable non-reset zone / address
Zone/address 000/00 non-reset
Re-enable: push ACCEPT?
Re-enable non-reset zone / address
Operating Instructions Fire alarm system EBL512 V2.3.x
ACCEPT? H2
ACCEPT? B1
ACCEPT? B7
ACCEPT? B7
84
Comments
According to chapter
"Access", see page 72.
If there are no zone /
addresses to re-enable,
L
menu B7 will be shown
again.
L=a list in which you can
scroll.
If it's the correct zone /
address to re-enable, press
"A" to accept. If not, scroll
or write the wanted zone /
address and press "A" to
accept.
If more re-enablements
shall be done, continue like
above. If not, scroll or
press "Return" to menu
H2. Scroll or press
"Return" to log off.