Exercise caution because the device is still energized after it is shut down on the
controller home screen.
Step 2 Open the adjustable side panel, remove the cover from the water pump
connection box, and remove the cables.
Step 3 Remove the water pump.
1.
2.
Step 4 Install the new pump on the smart cooling product and install the water pump
cables, and connection box cover.
Step 5 Install the adjustable side panels.
Step 6 Power on the device, choose Maint > Performance Maint on the home screen to
access the performance maintenance screen, and clear the total runtime of the
spray pump.
Step 7 Tap Start on the home screen. Ensure that the smart cooling product is running
normally without any alarms.
----End

8.4.19 Replacing a Switch

Issue 01 (2021-01-30)
NO TICE
Remove the water inlet and outlet pipes of the water pump.
Remove the fasteners from the water pump using a socket wrench, and pull
out the pump.
Figure 8-33 Removing a water pump
Copyright © Huawei Technologies Co., Ltd.