FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Figure 4-14 Requirement for wrapping the electric heating belt
● The electric heating belt needs to be wrapped evenly on the drainpipe and
water refill pipe during onsite construction.
● Wrap the electric heating belt and then wrap the thermal insulation foam.
Ensure that the thermal insulation foam covers the temperature control switch
and temperature sensor probe. The thermal insulation foam must withstand a
temperature above 200°C.
4.3.6 Removing Transport Fasteners and Desiccant Bags
Procedure
Step 1 Remove the adjustable side panels outside the compressors and take out the
desiccant bags from the compressors.
Figure 4-15 Positions of the desiccant bags
Step 2 Open the electric control box and take out the desiccant bags.
Step 3 Loosen the three transport fixing bolts of the compressor using a 13# solid wrench
and remove the sheet metal fasteners.