Item
Condensate
water pan
drainpipe

3.2.3 Pipe Supports

The following figure shows pipe supports. The supports used onsite prevails.
Figure 3-3 Pipe supports (unit: mm)

3.2.4 Cable

Waterproof connectors for cables should be designed according to the
recommended cable specifications in the following table. If the cable used onsite
does not meet the recommended specifications, the cable may fail to be routed
through the waterproof connector or the waterproof connector may fail to be
secured.
Issue 01 (2021-01-30)
Connector
G 1 inch
external
thread
connector
NO TE
● U-shaped pipe clamp height H = Pipe diameter (including the thermal insulation foam)
– 5 mm
● Install supports every 2500 mm in the straight sections of pipes, and 1000 mm away
from each bending point in the turning sections.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
3 System Installation (Building Scenario)
Dimensions
Material
DN32
Rigid pipe (made of
PP-R, C-PVC, or
other materials)
Descriptio
n
33