Replacing An Air Supply Fan - Huawei FusionCol8000-E240 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Step 7 Bind the cable ties.
Step 8 Power on the device and tap Start on the home screen. Ensure that the device is
running properly without generating alarms.
----End

8.4.12 Replacing an Air Supply Fan

Prerequisites
Procedure
Step 1 On the controller home screen, tap Shutdown and turn off the device switch in
the PDF.
Exercise caution because the device is still energized after it is shut down on the
controller home screen.
Step 2 Remove the adjustable side panel and water barrier of the air supply fan to be
replaced.
Step 3 Cut off the cable ties that bind the cable connected to the faulty fan, and remove
the fan terminal.
Step 4 Before replacing the fifth air supply fan, remove the post, pipe, and baffle plate in
front of the fan.
Issue 01 (2021-01-30)
A fan needs to be replaced.
A spare fan of the same model is available and functional.
Tools: protection gloves, Phillips screwdriver, diagonal pliers, cable tie
NO TICE
Copyright © Huawei Technologies Co., Ltd.
8 System Maintenance
155