Electrical Connections; Safety Instructions - ABB TZIDC Manual

Table of Contents

Advertisement

18
TZIDC DIGITAL POSITIONER | CI/TZIDC/ATEX/IECEX-EN REV. C
... 5 Installation

Electrical connections

Safety instructions

DANGER
Risk of explosion for devices with local communication
interface (LCI)
A local communication interface (LCI) may not be operated in
hazardous areas.
Never use the local communication interface (LCI) on the
main board in a hazardous area!
WARNING
Risk of injury due to live parts!
When the housing is open, contact protection is not provided
and EMC protection is limited.
Before opening the housing, switch off the power supply.
The electrical connection may only be established by authorized
specialist personnel.
Notices on electrical connection in this instruction must be
observed; otherwise, electric safety and the IP-rating may be
adversely affected.
Safe isolation of electric circuits which are dangerous if touched
is only guaranteed when the connected devices fulfill the
requirements of EN 61140 (basic requirements for secure
separation).
To ensure safe isolation, install supply lines so that they are
separate from electrical circuits which are dangerous if touched,
or implement additional isolation measures for them.