NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
Installation Requirements
Table 2-3 Installation Requirements
Item
Room door
Floor
Pipe routing
Cabling
mode
Drainage
requirements
Water supply
requirements
of wet film
Power
distribution
Operating Specifications
Table 2-4 Operating specifications
Item
Operating ambient
temperature
Issue 03 (2020-08-30)
NetCol5000-C065
2 m high cabinet: width ≥
1.2 m, height ≥ 2.3 m. The
cabinet may topple over in
a short time.
Floor bearing capacity ≥ 530kg/m
Floor height ≥ 250 mm
Bottom pipe routing
Top cabling
Automatic drainage
The inlet water pressure should be in the range of 0.1–0.7 MPa
(A reducing valve must be installed if the inlet water pressure
exceeds 0.7 MPa.), and the temperature should be in the range
of 1°C–40°C.
The wet film humidifier should use tap water (no water
treatment facility needed for the inlet water) that meets the
following requirements:
● Non-freezing and nephelometric turbidity units (NTU): < 3
● No visible substances
● 6.5 ≤ pH value ≤ 8.5
● Total hardness (in CaCO
Leakage circuit breakers are not used for the main power route.
If leakage circuit breakers are required by the customer or by
local regulations, use the residual current circuit breakers
(RCCBs) that are not sensitive to the single-phase DC pulses and
transient current pulses.
NetCol5000-C065
4–55°C
Copyright © Huawei Technologies Co., Ltd.
2 Product Description
NetCol5000-C030/C032
● 2 m high cabinet: width ≥ 1.2
m, height ≥ 2.3 m. The cabinet
may topple over in a short time.
● 2.2 m high cabinet: width ≥ 1.2
m, height ≥ 2.5 m. The cabinet
may topple over in a short time.
2
): ≤ 450 mg/L
3
NetCol5000-C030/C032
24