NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
Parameter
Requirement
control
Issue 03 (2020-08-30)
Description
Enable or disable the
requirement control
for the master device.
● When the
requirement
control is Disable,
the master device
does not
synchronize data
to the slave
device, and all the
smart cooling
products operate
based on their
own requirements,
not referring to
the mode
delivered by the
master device.
● When the
requirement
control is Anti-
competitive
running, the
master device
synchronizes data
(the temperature
and humidity
control type and
set points of the
master device and
other parameters)
to the slave
device, and all the
smart cooling
products in the
group refer to the
mode delivered by
the master device.
● When the
requirement
control is Indoor
fan unified
control or Central
load distribution,
all smart cooling
product fans in the
Copyright © Huawei Technologies Co., Ltd.
Configuration
Principle
Anti-competitive
running is
recommended for the
following scenario: In
one teamwork, the
temperature and
humidity control type
and temperature and
humidity set point of
units are the same, and
device heat loads are
distributed evenly.
4 Commissioning
Default
Value
Disable
95