Exercise caution because the device is still energized after it is shut down on the
LCD.
Step 2 Open the rear door and remove the air filter.
Step 3 Flip up the rectifier clip.
Step 4 Take out the handle and pull out the rectifier from the subrack.
Figure 6-15 Replacing a rectifier (NetCol5000-C065)
Figure 6-16 Replacing a rectifier (NetCol5000-C030/C032)
Step 5 Remove the old rectifier, insert the new rectifier to the corresponding slot, and flip
down the clip to lock the rectifier.
Step 6 Install the air filter. Close and lock the rear door.
----End
Issue 03 (2020-08-30)