Parameter
Networking
mode
Number of
air
conditioners
in this group
Number of
running air
conditioners
in this group
Rotation
function
Rotation
period
Rotation
time
Issue 03 (2020-08-30)
Description
Networking mode for
the teamwork. The
networking mode set
on the screen must
be consistent with
the actual
networking mode.
Otherwise, the
teamwork control
function will be
unavailable. If the
networking mode
changes, select the
corresponding
networking mode on
the screen.
Number of the smart
cooling products in
this group (1 to 32
can be set).
Number of active
units in a group. The
value ranges from 1
to Number of air
conditioners in this
group.
Disable or enable the
active and standby
smart cooling
products to change
identity after a
certain time,
maximizing their
service life.
Rotation days (1–30).
24 hours in a day (0–
23).
Copyright © Huawei Technologies Co., Ltd.
Configuration
Principle
Networked over CAN or
MAC_CAN. CAN
network indicates
teamwork control over
a CAN bus, MAC_CAN
network teamwork
control over an FE port.
If the device is
connected to the smart
ETH gateway or
ECC800, set the
parameter to
MAC_CAN network. In
other scenarios, set the
parameter to CAN
network.
Total number of the
smart cooling products
in this group.
The host allocates
running units by smart
cooling product unit
address in ascending
order, which is from 1
to 32. The rest will
become the standby
ones.
This function is
recommended when the
heat is even.
7 by default
0 by default
4 Commissioning
Default
Value
CAN network
3
2
Disable
7 day (s)
0