Huawei NetCol5000-C030H90D0 User Manual page 148

In-row chilled water smart cooling product
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
Alar
m ID
A105
A118
A130
A193
A220
A233
Issue 03 (2020-08-30)
Alarm
Alarm
Name
Severi
ty
Indoor fan
CRITC
failure alarm
AL
Primary
MAJO
power
R
failure alarm
Humid
MAJO
water inlet
R
solenoid
valve fault
Air-side diff
MAJO
pressure
R
sensor fault
Wizard
WARNI
startup is in
NG
progress
Air-side low
WARNI
pressure
NG
difference
alarm
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible Cause
1. The indoor fan is
faulty.
2. The cable to the
Indoor fan is not
connected properly.
3. The power supply
to the Indoor fan is
abnormal.
The power supply is
faulty.
1. The cables to the
water inlet solenoid
valve are loose or
damaged.
2. The water inlet
solenoid valve is
faulty.
1. The differential
pressure sensor
cable is loose or
damaged.
2. The pressure tube
of the differential
pressure sensor is
reversely connected.
3. The differential
pressure sensor is
faulty.
Wizard startup is in
progress.
1. Contained aisles
are poorly-sealed.
2. The differential
pressure sensor is
faulty.
Solution
1. Maintain or replace
the Indoor fan.
2. Check the cable
connection to the
Indoor fan.
3. Check the power
supply to the Indoor
fan.
Check the power supply.
1. Check the cables to
the water inlet solenoid
valve.
2. Replace the water
inlet solenoid valve.
1. Check the cable
connection to the
differential pressure
sensor.
2. Check the tube
connection to the
differential pressure
sensor.
3. Maintain or replace
the differential pressure
sensor.
Wait until wizard
startup is complete or
clear the Wizard startup
in progress alarm
manually to exit wizard
startup.
1. Check that the cold
and hot aisles are well-
sealed.
2. Maintain or replace
the differential pressure
sensor.
140