NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
Figure 3-42 Connecting an equipotential PE cable (NetCol5000-C030/C032)
3.12.3 Connecting Power Cables
Prerequisites
Check that the voltage is less than 1 V between wires by using a multimeter
before connecting power cables.
Procedure
Step 1 Take out OT terminals and cord end terminals from the fittings bag, and prepare
cables.
● Crimp the cables firmly and ensure that they are not loose after pulling.
● If the cables are not recommended specifications, you need to prepare the
terminals by yourself.
Step 2 Remove the cover of the electric control box.
1.
2.
3.
Issue 03 (2020-08-30)
NO TICE
NO TICE
Remove the four screws from the cover of the electric control box using an
M5 screwdriver.
Push the cover upward and take out the cover from the positioning pins.
Pull the entire cover out of the cabinet.
Copyright © Huawei Technologies Co., Ltd.
3 Installation
63