Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative Cooling
System
User Manual
Figure 3-18 Connecting the equipment to the air duct
(1) Connection between the air duct and canvas
(B) Canvas
(D) Equipment
Step 6 Wrap the rubber plastic thermal insulation foam (at least 3 cm thick, covering the aluminum
foil) for the canvas.
Figure 3-19 Warping thermal insulation foam for the canvas
Step 7 Use M12 screws to secure the air duct.
Issue 02 (2019-10-10)
Copyright © Huawei Technologies Co., Ltd.
3 Installation Guide
(A) Canvas sheet metal
(C) Thermal insulation foam
38