Huawei NetCol8000-E220 User Manual page 191

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative Cooling
System
User Manual
Context
Be careful when configuring alarms. Only professional maintenance personnel can change
alarm settings.
Procedure
Step 1 Choose Settings > Alarm Settings > T/H Sensor on the home screen.
displayed.
Figure 7-7 Setting alarm parameter 1
Step 2 Tap Threshold following Supply air high temperature alarm.
Step 3 Set the value to 45 and tap
Issue 02 (2019-10-10)
Cold aisle high temperature alarm threshold + 5°C ≤ Return air high temperature alarm
threshold
Supply air low temperature alarm threshold + 5°C ≤ Return air low temperature alarm
threshold
To set an alarm threshold, follow the instructions in this section.
The method for setting each alarm is the same. This section describes how to set
Threshold of Supply air high temperature alarm to 45.
If you need to change alarm settings, log in as the Admin user.
Copyright © Huawei Technologies Co., Ltd.
, as shown in
Figure
7-8.
7 FAQ
Figure 7-7
is
183