NetCol8000-E220 Modular Indirect Evaporative Cooling
System
User Manual
Procedure
Step 1 On the controller home screen, tap Shutdown to turn off the fan switch.
Step 2 Open maintenance door 1, enter the equipment, push the maintenance door leading to the
upper layer upward, and enter the upper layer.
Step 3 Cut the cable tie that binds the cable connected to the faulty fan, and remove the fan terminal.
Step 4 Remove screws from the fan support.
Figure 6-4 Removing the screws from the fan support
Step 5 Remove the six screws from the fan support and fan to separate the fan support from the fan.
Issue 02 (2019-10-10)
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
159