Huawei NetCol8000-E220 User Manual page 154

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative Cooling
System
User Manual
Alarm
Alarm
ID
Severity
A28B-
MAJOR
01
A28B-
CRITICA
02
L
Issue 02 (2019-10-10)
Alarm
Probable Cause
Name
unit has an open phase, incorrect
phase sequence, or is unavailable.
7. Cables to the indoor or outdoor
fan are not properly connected.
8. The outdoor fan or its drive is
faulty.
9. The exhaust fan is faulty.
Comp 2 high
1. The refrigerant leaks.
discharge
2. The condenser fins are dirty or
temperature
blocked.
alarm
3. The ambient temperature exceeds
the upper threshold.
4. The temperature displayed by the
exhaust air temperature sensor is
different from the actual
temperature.
5. The exhaust air temperature
sensor is faulty.
6. The input power of the outdoor
unit has an open phase, incorrect
phase sequence, or is unavailable.
7. Cables to the indoor or outdoor
fan are not properly connected.
8. The outdoor fan or its drive is
faulty.
9. The exhaust fan is faulty.
Comp 1 high
1. The refrigerant leaks.
discharge
2. The condenser fins are dirty or
temperature
blocked.
alarm
3. The ambient temperature exceeds
the upper threshold.
4. The temperature displayed by the
exhaust air temperature sensor is
different from the actual
temperature.
5. The exhaust air temperature
sensor is faulty.
6. The input power of the outdoor
unit has an open phase, incorrect
phase sequence, or is unavailable.
7. Cables to the indoor or outdoor
fan are not properly connected.
8. The outdoor fan or its drive is
faulty.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Solution
7. Check the cables to the indoor
and outdoor fans.
8. Maintain or replace the
outdoor fan or its drive.
9. Maintain or replace the
exhaust fan.
1. Identify and repair the leaking
point, and refill refrigerant after
maintenance.
2. Clean the condenser fins.
3. Measure the ambient
temperature.
4. Calibrate or replace the
temperature sensor.
5. Maintain or replace the
temperature sensor.
6. Check the input power of the
outdoor unit.
7. Check the cables to the indoor
and outdoor fans.
8. Maintain or replace the
outdoor fan or its drive.
9. Maintain or replace the
exhaust fan.
1. Identify and repair the leaking
point, and refill refrigerant after
maintenance.
2. Clean the condenser fins.
3. Measure the ambient
temperature.
4. Calibrate or replace the
temperature sensor.
5. Maintain or replace the
temperature sensor.
6. Check the input power of the
outdoor unit.
7. Check the cables to the indoor
and outdoor fans.
8. Maintain or replace the
outdoor fan or its drive.
9. Maintain or replace the
exhaust fan.
146

Advertisement

Table of Contents
loading

Table of Contents