Alarm Reference For The Independent Deployment Ai/Di Unit; Mue06A_Board Not Exist - Huawei ECC500 User Manual

Hide thumbs Also See for ECC500:
Table of Contents

Advertisement

ECC500
User Manual
6.2.3 Alarm Reference for the Independent Deployment AI/DI
Unit

6.2.3.1 MUE06A_Board Not Exist

Description
This alarm is generated when cables are not securely connected, the power supply is abnormal,
or the board is faulty.
Attribute
Alarm ID
22656
Impact on the System
After this alarm is generated, the WebUI stops updating parameter values of undetected
equipment and fails to send configuration signals. Maintain the equipment immediately.
Possible Causes
Procedure
Step 1 Check that cables are properly connected.
Step 2 Rectify faults in the power supply.
Step 3 Replace the faulty board.
----End
Clearing
This alarm is cleared when the board is properly connected and the communication between
the board and the ECC500 resumes.
Issue 04 (2019-12-20)
For details about the alarms and troubleshooting for the eight ports on the Independent Deployment
AI/DI Unit, see the alarm description and troubleshooting instructions provided for the AI/DI_1 port on
the AI/DI expansion card.
Cables are not securely connected.
The power supply is faulty.
The board is faulty.
Copyright © Huawei Technologies Co., Ltd.
Alarm Severity
Set to Major by default.
6 Maintenance and Troubleshooting
Alarm Type
Equipment alarm
59